<Spec id="492" path="\8\6\86d2213f59b4e6dddf914ef8dae7ca5a.pdf"><Text id="92386" page="4">The high temperature design should be based on hybrid insulation system. The average temperature rise of the transformer windings at rated power should not exceed 95 K, and the top oil temperature should not exceed 60 K. Reference to other requirements in IEC 60076-14.</Text></Spec>